PMCS Interface Toolkit Back to Main Menu •••• iPOWER LEADER TMPMCS 6.11aInterface ToolkitInstallation GuideGEH-6513GE Power Management Control Syste
2 PMCS Interface Toolkitof power management devices, complete with working controls that arelinked to the corresponding devices in your facility.• Ch
92 PMCS Interface Toolkit565 Feeder Management RelayThe large faceplate representation of the 565 provides the following animatedfunctions:Feature Fun
93Page Value Text Displayed Description1 ACTUAL VALUESCURRENTPage header2 PHASE A CURRENTxxxValue in amps3 PHASE B CURRENTxxxValue in amps1 4 PHASE C
94 PMCS Interface ToolkitPage Value Text Displayed Description3 INST PHASE O/CTRIPS ###4 TIMED GROUND O/CTRIPS ###4 5 INST GROUND O/CTRIPS ##
95Page Value Text Displayed Description17 TIME OVERCURRENTPHASE ABCorTIME OVERCURRENT GROUNDorINST OVERCURRENT PHASE ABCorUNDERVOLTAGE FAULTorOVERVOLT
96 PMCS Interface ToolkitPage Value Text Displayed Description1 ACTUAL VALUES VOLTAGEPage header2 VOLTAGE A-B xxx.xx kV6 3 VOLTAGE B-C xxx.xx kV4 V
97Page Value Text Displayed Description10 PEAK KVAR DEMAND xxx kVARorKVAR DEMANDDISABLEDorDisplayed if disabled11 CLEAR KVAR DEMANDDATA? NOPress
98 PMCS Interface Toolkit(This page left blank intentionally)
99Features of Tabular Data ScreenWizardsIntroductionThis chapter describes the features available with tabular data screens. The set offeatures basic
100 PMCS Interface ToolkitThe right side of the screen contains a display of the device data. The tabs at thebottom enable you to select among the var
101Power Leader EPMThe Power Leader EPM Tabular Data Screen wizard provides the followingcommand buttons:Tab Button FunctionSetup Meter Initialize Per
3ConventionsYou will find this book easy to use if you look for these simple conventions:• Boldface type indicates the name of an item you need to se
102 PMCS Interface ToolkitSpectra MicroVersaTripThe Spectra MicroVersaTrip Tabular Data Screen wizard provides the followingcommand buttons on the Set
103Enhanced MicroVersaTrip-C Trip UnitThe Enhanced MicroVersaTrip-C Tabular Data Screen provides six push buttons onthe Setup screen:Tab Button Functi
104 PMCS Interface ToolkitEnhanced MicroVersaTrip-D Trip UnitThe Enhanced MicroVersaTrip-D Tabular Data Screen provides six push buttons onthe Setup t
105POWER LEADER MeterThe POWER LEADER Meter Tabular Data Screen wizard provides three pushbuttons on the Command screen:Tab Button FunctionCommand Ene
106 PMCS Interface ToolkitSpectra ECMThe Spectra ECM Tabular Data Screen wizard performs the following actions withpush buttons on the Command screen:
107MDP Digital Overcurrent RelayThe feature to bear in mind when working with the MDP tabular wizard is:• On the Setup screen, you must enter a value
108 PMCS Interface ToolkitCommand TabThe MDP Tabular Data Screen wizard has three command buttons:Tab Button FunctionCommand Open Breaker Opens the br
109Setup TabThe MDP Setup Screen shows:• Phase Settings Configuration• Ground Settings ConfigurationYou must enter CT Ratio in the relevant field.
110 PMCS Interface ToolkitPQM (Power Quality Meter)All six function buttons under the Info box are enabled for the PQM.The PQM Tabular Data Screen wiz
111Metering TabThe Multilin PQM Metering tab shows:• Metering values: For A, B, C and 3 Phase• Energy: In various values• Output Relays: Alarm, Au
4 PMCS Interface ToolkitFrom the InTouch Configuration menu, select Install Wizards.The Wizard Installation dialog displays two list boxes, showing th
112 PMCS Interface ToolkitStatus TabThe Multilin Status tab shows the status of Alarms, Aux1, Aux2, Aux3 Relays.
113Demand TabThe Multilin PQM Demand screen shows :• Demand Current & Power• Peak Demand• Minimum and Maximum Frequency and their Time Stamps.T
114 PMCS Interface ToolkitIV Range TabThe Multilin PQM IV Range tab shows the Minumum and Maximum Current, Voltage Values.The Clear Current Min/Max bu
115P Range TabThe Multilin PQM Power Range screen shows the Power minimum and maximum values.The Clear Power Min/Max button, when clicked, will clear
116 PMCS Interface ToolkitAnalysis TabThe Multilin PQM Power Analysis screen shows:• Power Quality Values• Total Harmonic Distortion• THD MaxThe Cl
117IO TabThe Multilin PQM Inputs and Outputs screen shows:• Digital Input Switches• Output Relays• Analog Input• Switch Input Pulse CountersThe Re
118 PMCS Interface ToolkitSetpoints TabThe Multilin PQM System Setpoints screen shows:• Current Demand Type• Current Demand Time Interval (m)• Powe
119Motor Manager II (MMII)Five of the six function buttons under the Info box are enabled for the MMII; theWave button is not supported for the MMII.T
120 PMCS Interface ToolkitEPM 3710 MeterThe EPM 3710 Tabular Data Screen wizard provides the following special features:• The Normal Metering Values
121EPM 3720 MeterThe EPM 3720 Tabular Data Screen wizard has several special features. You can usethe Setup 1, Setup 2, and Setpoints screens to chang
5Using and ConfiguringPMCS WizardsAbout the WizardsThe wizards contained in the PMCS Interface Toolkit allow you to quickly buildaccurate and friendly
122 PMCS Interface ToolkitEPM 7300 MeterThe EPM 7300 Tabular Data Screen wizard has several special features. You can usethe Setup screen to change th
123Metering TabThe 7300 ION Normal Metering Values screen shows the metering values:• A, B and C• Three Phase Values• Voltage Imbalance• Current I
124 PMCS Interface ToolkitMin/Max TabThe 7300 ION Min/Max/Demand Values screen shows:• Minimum and maximum metering values• Digital Outputs1. By cl
125Setup TabThe 7300 ION Setup screen shows various setup values of the device such as Volts Mode, Phase Order, PT Secondaryand CT Secondary.The Downl
126 PMCS Interface ToolkitEPM 7330 MeterThe EPM 7330 Tabular Data Screen wizard has several special features. You can usethe Setup screen to change th
127Metering TabThe 7330 ION Normal Metering Values screen shows the metering values:• A, B and C• Three Phase Values• Voltage Imbalance• Current I
128 PMCS Interface ToolkitMin/MaxThe 7330 ION Min/Max/Demand Values screen shows:• Minimum and maximum metering values• Digital Outputs1. By clicki
129Setup TabThe 7330 ION Setup screen shows various setup values of the device such as Volts Mode, Phase Order, PT Secondaryand CT Secondary.The Downl
130 PMCS Interface ToolkitEPM 7500/7600 MeterThe EPM 7500/7600 Tabular Data Screen wizard has several special features. Youcan use the Setup screen to
131• I C: n/a when Voltage Mode is SINGLE• KW A, B: n/a when Voltage Mode is DELTA• KW C: n/a when Voltage Mode is DELTA or SINGLE• KW Total• KVA
6 PMCS Interface ToolkitSmall Faceplate WizardsUsageThe Small Faceplate wizards are icon-sized graphics typically used to create accurateelevation vie
132 PMCS Interface ToolkitMin/Max TabEPM 7500/7600 Meter - Min/Max TabThe Minimum/Maximum Values tab displays a variety of minimum and maximumvalues r
133• FrequencyPower Quality TabEPM 7500/7600 Meter - Power Quality TabThe Power Quality tab displays the following power quality values from the EPM7
134 PMCS Interface ToolkitEnable/Disable Sag Swell – Enables or Disables Sag Swell Tracking.Enable/Disable Over KW SWD – Enables or Disables Over Real
135• Average RMS Current Sliding Window Demand, Predicted Demand,and Thermal DemandMinimum/Peak Demand• Minimum or Peak Real Power Sliding Window De
136 PMCS Interface Toolkit• Status (On, Off) for Status Inputs (SI) 1-8. (Color Code: Green – ON,Grey – OFF).• Counters for SI1-8. The Inputs tab al
137• Neutral CT Primary and SecondaryCommunications• Baud Rate for Comm 1, 2, and 3.• Unit ID for Comm 1, 2, and 3.• Protocol for Comm 1, 2, and 3
138 PMCS Interface ToolkitSetup 2 TabEPM 7500/7600 Meter - Setup 2 TabThe Setup 2 tab displays the following demand values from the EPM 7500/7600.Slid
139• Over Pickup for Over KW, Over Current, and Over Vunbal.• Time On for Over KW, Over Current, and Over Vunbal.• Time Off for Over KW, Over Curre
140 PMCS Interface ToolkitEPM 7700 MeterThe EPM 7700 Tabular Data Screen wizard has several special features. You can usethe Setup screen to change th
141• KW A, B: n/a when Voltage Mode is DELTA• KW C: n/a when Voltage Mode is DELTA or SINGLE• KW Total• KVAR A, B: n/a when Voltage Mode is DELTA•
7Enter the name of the windowto open when the icon isclicked on during runtime.
142 PMCS Interface ToolkitMin/Max TabEPM 7700 ION Meter - Min/Max TabThe Minimum/Maximum Values tab displays a variety of minimum and maximumvalues re
143Power Quality TabEPM 7700 ION Meter - Power Quality TabThe Power Quality tab displays the following power quality values from the EPM7700.Disturban
144 PMCS Interface ToolkitThe Power Quality tab also provides push buttons for performing the followingcommands:Reset Disturbance Counters – Resets Sa
145• Average RMS Current Sliding Window Demand and Predicted DemandThermal Demand• Real Power Thermal Demand• Reactive Power Thermal Demand• Appar
146 PMCS Interface Toolkit• Full Scale Setting for AI1-4. : n/a when doesn’t exist on the meter• Scaled Value for AI1-4. : n/a when doesn’t exist on
147Communications• Baud Rate for Comm 1, 2, and 3.• Unit ID for Comm 1, 2, and 3.• Protocol for Comm 1, 2, and 3.• Mode for Comm 1.• Ethernet Pro
148 PMCS Interface ToolkitSetup 2 TabEPM 7700 ION Meter - Setup 2 TabThe Setup 2 tab displays the following demand values from the EPM 7700.Sliding Wi
149• Over Pickup for Over KW, Over Current, and Over Vunbal.• Time On for Over KW, Over Current, and Over Vunbal.• Time Off for Over KW, Over Curre
150 PMCS Interface ToolkitUniversal RelayThe Universal Relay devices are a highly-flexible family of power managementdevices based on the concept of a
151Metering TabUniversal Relay - Metering Data ScreenThe Metering tab displays the following metered values from the B30, C60, D60,F30, F35, F60, G60,
8 PMCS Interface ToolkitLarge Faceplate WizardsUsageLarge Faceplate wizards are three-dimensional representations of device faceplatesthat can be used
152 PMCS Interface ToolkitPower FactorShows the signed power factor value in percent.Power Factor values derived from a source wired in a delta config
153VoltagePhasor magnitude and angle for negative, positive and zero sequence voltages.Voltage values derived from a source wired in a delta configura
154 PMCS Interface ToolkitThe label color indicates thefunction’s availability on theconnected device: gray = notavailable, black = available.Button
155Current Transformers (CT)Primary: indicates the current rating of the CT primary.Secondary: indicates the output current of the CT secondary, eithe
156 PMCS Interface ToolkitTransformer TabUniversal Relay - Transformer TabThe T60 device alone supports a Transformer Tab on its wizard. This tab is u
157Elements TabUniversal Relay - Digital Elements TabThe Elements tab displays user-defined name and current status of the sixteen digitalelements in
158 PMCS Interface ToolkitDigital Counter TabUniversal Relay - Digital Counter TabThe digital counter tab supports B30, C30, C60, D60, F30, F35, F60,
159Virtual Inputs TabUniversal Relay - Virtual Inputs TabThe Virtual Inputs (VInputs) tab allows the user to enable/disable all configuredvirtual inpu
160 PMCS Interface ToolkitVirtual Outputs TabUniversal Relay - Virtual Outputs TabThe Virtual Outputs (VOutput) tab allows the user to view the status
161Contact Inputs TabUniversal Relay - Contact Input TabThe Contact Input tab supports the B30, C30, C60, D60, F30, F35, F60, G60, L60,L90, M60 and T6
9ConfigurationPlace the Large Faceplate wizard into an open window, then double-click on it todisplay the Large Faceplate Dialog box. Configure the wi
162 PMCS Interface ToolkitContact Output TabUniversal Relay - Contact Output TabThe Contact Output tab supports the B30, C30, C60, D60, F30, F35, F60,
163DCMA TabUniversal Relay - DCMA TabThe Direct Current MilliAmperes (DCMA) tab supports the B30, C30, C60, D60,F30, F35, F60, G60, L60, L90, M60 and
164 PMCS Interface ToolkitSource TabsUniversal Relay - Source Tab ExampleSimilar in operation to the metering tab (except that frequency information i
165Demand TabUniversal Relay - Demand TabThe Demand tab supports the B30, C60, D60, F30, F35, F60, G60, L60, L90, M60and T60 UR devices, and shows a v
166 PMCS Interface ToolkitLine TabUniversal Relay - Line TabThe Line tab supports the D60, F30, F60, G60, L60, L90 and UR devices, and showsa variety
167Breaker TabUniversal Relay - Breaker TabThe Breaker tab supports the B30, C30, C60, D60, F30, F35, F60, G60, L60, L90,M60 and T60 UR devices, and s
168 PMCS Interface ToolkitAuto RecloseIf the breaker is so equipped, the status of and reclose count for up to six AutoReclose functions can be displa
169Remote Temperature Detection TabUniversal Relay - Contact Output TabThe RTD tab supports the B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60a
170 PMCS Interface ToolkitBus TabUniversal Relay - Bus TabThe Bus tab is supported for the B30 UR device only. It displays Phase Magnitudeand Angle me
171239 Motor Protection RelayThe 239 does not support Waveform Capture or Event generation, therefore thesebuttons are disabled beneath the Info box.T
10 PMCS Interface ToolkitAlso, the Application Name field must be completed as ION_LINK rather thanGE32MODB or GE32MTCP for the EPM7700 device. The IO
172 PMCS Interface ToolkitThe Reset Device button, when clicked, will issue a RESET command to the 239.The Emergency Restart button, when clicked, wil
173Trip DataThe Multilin 239 Last Trip Data screen shows:• Cause of Last Trip and their corresponding currents and RTD Temperatures at the time of tr
174 PMCS Interface ToolkitSetpoints TabThe Multilin 239 System Setpoints screen shows:• CT Inputs• Motor Data• Phase Current Overload• Breaker Fai
175269 Plus Motor Management RelayThe 269 Tabular Data Screen wizard provides two reset push buttons on the Setup 6tab.Tab Button FunctionStatus 6 Cle
176 PMCS Interface Toolkit369 Motor Management RelayMetering Tab369 - Metering Data ScreenThe Metering tab displays the following metered values from
177Average Line-Neutral voltage. (only shown for wye configurations)PowerPower values are displayed only if the Metering or Backspin option is install
178 PMCS Interface ToolkitAlarms Tab369 Relay - Alarms TabThe Alarms tab consists of three pages – Status, Trip Data, and Trip Counters. Youcan navig
179Demand Tab369 Relay - Demand TabThis tab displays current and power demand metering information.Current demand is indicated regardless of options/V
180 PMCS Interface ToolkitLocal RTD Tab369 Relay - Local RTD TabThis tab displays information about any RTD temperature probes connected directlyto th
181Remote RTD Tab369 Relay - Remote RTD TabThis tab displays information about any RTD temperature probes connected to one ormore Remote RTD units. Th
11Tabular Data Screen WizardsUsageTabular Data Screen wizards contain organized, comprehensive, tabular layouts ofdevice parameters including addition
182 PMCS Interface ToolkitControl Tab369 Relay - Control TabThis tab provides limited control functionality over Modbus.Status – indicates the current
183Setup Tab369 Relay - Setup TabThis tab displays selected setpoints from the device. All fields on this tab are read-only. Setpoints may be changed
184 PMCS Interface ToolkitSR469 Motor Management RelayAll six function buttons under the Info area are enabled for the SR469.The SR469 Tabular Data Sc
185Volts AB, Volts BC and Volts CA. Also shows Power, Energy, Motor Data and RTD information.The Clear Peak Demand button will clear all Peak Demand d
186 PMCS Interface ToolkitAlarms TabThe Multilin SR469 Alarm Status screen shows the status of various alarms such as Overload Alarm and UnderpowerAla
187Trip TabThe Multilin SR469 Trip screen shows the values of last trip data.The Clear Last Trip Data button will clear all values of the last trip da
188 PMCS Interface ToolkitIO TabThe Multilin SR469 Inputs & Outputs screen shows values related to:• Output Relays• Digital Input Switches• Ana
189Maintenance TabThe Multilin SR469 Maintenance screen shows values related to:• Trip Counters• Timers• General CountersThe Clear Trip Counters bu
190 PMCS Interface ToolkitAnalog TabThe Multilin SR469 Analog Input Differential screen shows:• Analog Input Diff 1-2• Analog Input Diff 3-4
191RTD HI TabThe Multilin SR469 HI Alarm Status screen shows various RTD values.Setpoints TabThe Multilin SR469 System Setpoints screen shows values o
ii •••• Back to Main Menu PMCS Interface ToolkitNoticeThe information contained in this document is subject to change without notice. GE makes no wa
12 PMCS Interface ToolkitEnter the unique eight- charactername matching the appropriateTopic in the PMCS DDE Server.Use the Group Name field to logica
192 PMCS Interface ToolkitSR489 Generator Management RelayAll the SR489’s function buttons below the Info box are enabled.The SR489 Tabular Data Scree
193• Demand• Power• RTD Information• Motor DataThe Clear Peak Demand button clears all peak demand values.The Clear MWh & Mvarh button clears
194 PMCS Interface ToolkitThe Multilin SR489 Alarm Pickups screen shows all the Alarms.Trip Data TabThe Multilin SR489 Last Trip Data screen shows the
195IO TabThe Multilin SR489 Inputs & Outputs screen shows:• Digital Input Switches• Analog Inputs• Output Relays• Learned Data ValuesThe Clear
196 PMCS Interface ToolkitMaintenance TabThe Multilin SR489 Maintenance screen shows:• General Timers & Counters• Trip CountersThe Clear Trip Co
197Setpoints TabThe Multilin SR489 System Setpoints screen shows various values related to the setpoints such as Phase CT Primary,Ground CT Type, VT C
198 PMCS Interface Toolkit565 Feeder Management RelayThe 565 Tabular Data Screen wizard has the following buttons on the Command tab:Tab Button Functi
199scaled to display any desired units from the front of the device, but these labels arenot sent to the DDE Server.For complete explanations of param
200 PMCS Interface Toolkit735 Feeder RelayThe Events and Wave function buttons below the Info box are disabled since the 735does not support Waveform
201Trip Data TabThe 735 Trip Data screen shows trip data information such as:• Last Trip Data• Trip RecordThe Clear Last 5 Trip Causes button will c
1340035, the GE 7700 Gateway Users Guide, and GEH-6514, PMCS Read This BookFirst, for more information on network configuration. The Node Name field i
202 PMCS Interface ToolkitSetpoints TabThe 735 System Setpoints screen shows setpoints information such as:• Dial Settings• Option Switches
203SR745 Transformer Management RelayUnder the Info area, the SR745’s function buttons are all enabled.The SR745 Tabular Data Screen wizard has three
204 PMCS Interface ToolkitFlags TabThe Multilin SR745 Element Flags screen shows the state and phases of various elements.IO TabThe Multilin SR745 Inp
205• Logic Inputs• Virtual Inputs• Output Relays• Virtual Outputs• Analog InputDemand TabThe Multilin SR745 Demand Data screen shows:• Configur
206 PMCS Interface ToolkitHarmonic TabThe Multilin SR745 Harmonic & Misc Data screen shows:• Harmonic Data• MiscThe Reset Loss of Life button wi
207Setpoints TabThe Multilin SR745 System Setpoints screen shows information such as Nominal Phase to Phase Voltage, Rated Load(MVA), Transformer Type
208 PMCS Interface ToolkitPower TabThe Multilin SR745 Power & Energy screen shows:• Power• Energy• Aging Factor• Tap Changer
209SR750/760 Feeder Management RelayThe SR750 and SR760 are very similar devices and share a common Tabular DataScreen wizard. During wizard configura
210 PMCS Interface ToolkitMetering TabThe SR750/760 Metering screen shows:• Current• Energy• Voltage• PowerThe Clear Energy Data button will clear
211Status TabThe SR750/760 Status screen shows Active Conditions.Fault TabThe SR750/760 Fault & Maintenance Data screen shows:
14 PMCS Interface ToolkitData Dialog box has an extra field for indicating when the RRTD option is installed.Be sure to select the correct RRTD option
212 PMCS Interface Toolkit• Fault Locations• Total Arcing CurrentThe Reset Arcing Current button will reset all values of the arcing current.Trip Ta
213Demand TabThe SR750/760 Demand screen shows details of:• Configuration• ValuesThe Reset Max Demand button will reset all maximum values of demand
214 PMCS Interface ToolkitLogic TabThe SR750/760 Logic screen shows:• Contact Inputs• Virtual Inputs• Logic Input StatesIO TabThe SR750/760 Inputs
215• Output Relays• Analog Input• Hardware Input Coils• Breaker OperationThe Open Breaker button will issue an Open Breaker command. The Close Bre
216 PMCS Interface ToolkitFanuc 90/30The Fanuc 90/30 Tabular Data Screen wizard is blank. This allows any desired datato be placed on the screen.Fanuc
217Fanuc Micro 90The GE Fanuc Micro 90 Tabular Data Screen is blank. This allows for any desireddata to be placed on the screen.
218 PMCS Interface ToolkitMX200The MX 200 device is an Automatic Transfer Switch. The Tabular Data Screen wizard has several special features. Youcan
219VoltagesNormal and Emergency Voltage values for all the phases.Timer Functions• Timer Active• Timer Countdown Value• Time on Emergency• No. of Tr
220 PMCS Interface ToolkitThe tab shows frequency and number of phases on source:• Position Status• Phase RotationThe status for Source is displayed a
221Control• YE• YN• No Load Test• Load Test• Fast Load Test• S5• S12• LS• Q7• Q3• Aux2• Aux1The legend is ON and OFF. If ON, it is indicated by amber
15Universal RelayThe Universal Relay device comes in several different models, and each modelsupports different capabilities, which are reflected by t
222 PMCS Interface Toolkit• Normal Pickup• Normal Dropout• Emer Pickup• Emer DropoutThe user can enter values against each parameter.Frequency (Hz)• N
223GEN PLCThe Generator Programmable Logic Controller (PLC) is a specially programmed PLC with specific number of I/Omodules, controlled by a Master P
224 PMCS Interface ToolkitGenerator TabThis tab displays generator parameters for 16 generators represented as G1 to G16 (buttons). When a button is
225Any alarm in generator’s status is displayed in amber. Otherwise the status is displayed in gray.Shutdown• Overcrank• Overspeed• High Water Temp• O
226 PMCS Interface ToolkitStatus• Latched Under Frequency• Latched Over Frequency• Communication Failure• Main Tank Low Fuel Level• Main Tank Critical
227EPM5300PThis device belongs to Electro Industries family, which is tightly integrated device in to PMCS product. This devicecontains the following
228 PMCS Interface ToolkitVoltage (Volts)• Phase (AN, BN, CN, AB, BC and CA)• Inst• THD Current• THD VoltageEnergy• WATT Hour• VA Hour• VAR HourPower•
229Setup One TabThe screen explains various parameters in relation with Relay 1 and Relay 2 such as:Configuration• Kilo Volt Inputs• Kilo Amp Input• M
230 PMCS Interface ToolkitReset• WATT Hour• VAR Hour• VA HourIf it is kilo volt inputs, the decimal placement is 2 (as shown in the screen); if kilo a
231LED display in Gray color: Limit 2 of the associated value is Set for Below.Exceeded Limit 1 LED display in GREEN color : The associated quanti
16 PMCS Interface ToolkitOne-Line WizardsUsageYou can use one-line wizards to create animated one-line diagrams that represent anelectrical schematic
232 PMCS Interface ToolkitEPM5200PThis device belongs to Electro Industries family, which is tightly integrated device in to PMCS product. This device
233Voltage (Volts)• Phase (AN, BN, CN, AB, BC, CA)• InstTHD Current/THD Voltage• Displays Phase A, Phase B and Phase C THD Current and Voltage values
234 PMCS Interface ToolkitConfiguration• Kilo Volt Inputs• Kilo Amp Input• Mega Watt Input• Phase Reverse Limits• Meter Setup• Limits Set ByRelay 1 /
235EPM5350PSpecial Note: This device supports GE32MTCP Server ONLY.This device belongs to Electro Industries family, which is tightly integrated devic
236 PMCS Interface Toolkit• THD Current• THD VoltageEnergy• WATT Hour• VA Hour• VAR HourPower• Real (WATT)• Reactive (VAR)• Apparent (VA)• PFSetup One
237• Meter Setup• Limits Set ByRelay 1 / Relay 2• Phase Reversal• Phase Imbalance• Delay On• Delay OffDecimal Placement• Volts Decimal Placement• Amps
238 PMCS Interface ToolkitLimit 1 Limit 1 value for the Associated quantity (For example: Phase A Amps)Trigger - Relay 1 LED display in Amber color :
239EPM5000PThis device belongs to the Electro Industries family, which is a tightly integrated device in to the PMCS product. Thedevice contains the f
240 PMCS Interface ToolkitSetupThe screen explains various parameters related to configuration and setup.Configuration: Mega WATT, Leading Zero, Reset
241EPM9450Q/EPM9650QThis device belongs to the Electro Industries family, which is a tightly integrated device in to the PMCS product.The device comes
17• Circuit Breaker wizards have two discrete color-change animations forOn/Off status display and one analog animation for a five-state display(Open
242 PMCS Interface ToolkitPF.• Frequency Normal/ High Speed: Displays Frequency in Hz.Min/MaxThe tab displays Maximum and Minimum values of various p
243DemandThe screen explains various parameters related to demand values:• Sliding Window Demand: Displays Average and Maximum Sliding window demand
244 PMCS Interface ToolkitThermal AverageThe screen explains about various parameters related to thermal average:• Current (Amps): Displays the curre
245Digital InputsThe Digital Inputs tab displays the following parameters of 8 digital inputs. They areName: Displays the name of the Digital Input. T
246 PMCS Interface ToolkitSetupThe screen explains various parameters related to setup.Current Set Points: Above and Below Current Setpoints are shown
247EPM7430D/EPM7450DThese devices belong to the Electro Industries family, which is a tightly integrated device in to the PMCS product.These devices c
248 PMCS Interface ToolkitMin/MaxThe tab displays Maximum and Minimum values of various parameters. The user can get maximum and minimumvalues by clic
249LimitsThe screen explains various parameters related to Limits and Triggers:Limit 1 Trigger/Limit 2 Trigger (Relay 1, Relay 2 and Relay 3)Relay 1,
250 PMCS Interface ToolkitTrigger - Relay 3 LED display in Amber color : Limit 1 of the associated value will trigger Relay 3.LED display in Gray colo
251SetupThe screen shows the following parameters in relation with Relay 1, Relay 2 and Relay 3 such as:Configuration: The Parameters under configurat
18 PMCS Interface ToolkitTransformer, Fuse, Ground, and Motor One-LineWizardsAfter placing a Fuse, Ground, or Motor wizard in a window, double-click o
252 PMCS Interface ToolkitTroubleshootingAssertion ErrorQ: While switching between InTouch's Runtime and Development modes, theprogram crashed wi
253Q: When I double-click the display on the PLEPM's Large Faceplate wizard to go tothe Tabular data screen, the DELTA metering tab is displayed,
255Appendix A:EPM 3720 Sliding WindowDemand KeysDownloading Sliding Demand Window Keys to the EPM 3720The EPM 3720 supports up to 10 sliding demand me
256 PMCS Interface Toolkit#1 #2 #3 & #4 Sliding Window Key Thumbwheel SettingsClass Sub-classInstance Measurement Supported Modes4 3 00 Volts LN A
257#1 #2 #3 & #4 Sliding Window Key Thumbwheel SettingsClass Sub-classInstance Measurement Supported Modes4 3 29-2F Reserved4 3 30 I2T Avg. (0 = O
258 PMCS Interface Toolkit#1 #2 #3 & #4 Sliding Window Key Thumbwheel SettingsClass Sub-classInstance Measurement Supported Modes4 3 88 V1 HD - Ha
259#1 #2 #3 & #4 Sliding Window Key Thumbwheel SettingsClass Sub-classInstance Measurement Supported Modes4 3 AE I3 HD - Harmonic #5 STD TD SD PD4
260 PMCS Interface Toolkit#1 #2 #3 & #4 Sliding Window Key Thumbwheel SettingsClass Sub-classInstance Measurement Supported Modes4 3 D4 I1 HD - Ha
261#1 #2 #3 & #4 Sliding Window Key Thumbwheel SettingsClass Sub-classInstance Measurement Supported Modes4 3 FA V3 HD - Harmonic #15 STD TD SD PD
19Horizontal and Vertical Relay One-Line WizardsAfter placing a Horizontal or Vertical Relay wizard in a window, double-click on itto display the dial
262 PMCS Interface Toolkit(This page left blank intentionally.)
263Appendix B:Automatic Waveform Capture andWaveform Retrieval on EPM3720Using a setpoint to trigger waveform capture or record on the EPM 3720When a
264 PMCS Interface ToolkitCapture Channel X where X represents an integer between 1 and 8.Following are the Channel assignments for Wye and Delta syst
265#1 #2 #3 & #4 Trigger Key Thumbwheel SettingClass Sub-class Instance Meaning0 0 00 Null Object Identifier1 0 00-05 Digital Inputs (Status Input
266 PMCS Interface Toolkit#1 #2 #3 & #4 Trigger Key Thumbwheel SettingClass Sub-class Instance Meaning4 A see validinstancesbelowThermal Demand Ma
267#1 #2 #3 & #4 Trigger Key Thumbwheel SettingClass Sub-class Instance Meaning17 kVAR Phase C STD TD SD PD18 kVA Total HS STD TD SD PD HRS19 kVA
268 PMCS Interface Toolkit#1 #2 #3 & #4 Trigger Key Thumbwheel SettingClass Sub-class Instance Meaning7B VAUX HD - Total Even STD TD SD PD7C I1 HD
269#1 #2 #3 & #4 Trigger Key Thumbwheel SettingClass Sub-class Instance MeaningA2 V3 HD - Harmonic #4 STD TD SD PDA3 VAUX HD - Harmonic #4 STD TD
270 PMCS Interface Toolkit#1 #2 #3 & #4 Trigger Key Thumbwheel SettingClass Sub-class Instance MeaningC9 V2 HD - Harmonic #9 STD TD SD PDCA V3 HD
271#1 #2 #3 & #4 Trigger Key Thumbwheel SettingClass Sub-class Instance MeaningF0 V1 HD - Harmonic #14 STD TD SD PDF1 V2 HD - Harmonic #14 STD TD
20 PMCS Interface ToolkitHorizontal and Vertical Switch One-Line WizardsAfter placing a Horizontal or Vertical Switch wizard in a window, double-click
272 PMCS Interface Toolkit#1 #2 #3 & #4 Trigger Key Thumbwheel SettingClass Sub-class Instance Meaning0A Amps Phase B HS STD TD SD PD0B Amps Phase
273#1 #2 #3 & #4 Trigger Key Thumbwheel SettingClass Sub-class Instance Meaning6E I3 HD - K-Factor STD TD SD PD6F I4 HD - K-Factor STD TD SD PD70
274 PMCS Interface Toolkit#1 #2 #3 & #4 Trigger Key Thumbwheel SettingClass Sub-class Instance Meaning95 I2 HD - Harmonic #2 STD TD SD PD96 I3 HD
275#1 #2 #3 & #4 Trigger Key Thumbwheel SettingClass Sub-class Instance MeaningBC I1 HD - Harmonic #7 STD TD SD PDBD I2 HD - Harmonic #7 STD TD SD
276 PMCS Interface Toolkit#1 #2 #3 & #4 Trigger Key Thumbwheel SettingClass Sub-class Instance MeaningE3 VAUX HD - Harmonic #12 STD TD SD PDE4 I1
277The action keys specify the instance number for an object to perform an action on.The following action keys are possible:Action Key SetpointSupport
278 PMCS Interface Toolkit(This page left blank intentionally.)
279Appendix C: EPM 7700 - SpecialConsiderationsEPM 7700 Tags Subject to Deactivation by Tabular Data Screen WizardThis appendix lists the EPM 7700 tag
280 PMCS Interface ToolkitMemory Discrete Comment Subject todeactivation?DeviceNm_CommFail Comm Fail Indicator for Pegasys DDE Server - ION_LINK NI/O
281Memory Discrete Comment Subject todeactivation?DeviceNm_26804_GWY Reset_Dist_Cnt NMemory Integer CommentDeviceNm_28672_Anlg PT Primary NDeviceNm_28
21Circuit Breaker One-Line WizardsAfter placing a Horizontal or Vertical Circuit Breaker wizard in a window, double-click on it to display the dialog
282 PMCS Interface ToolkitMemory Real CommentDeviceNm_28853_Anlg KVAR SWD SUB INTERVAL NDeviceNm_28854_Anlg KVA SWD SUBINTERVAL NDeviceNm_28855_Anlg I
283Memory Real CommentDeviceNm_29730_Anlg Over Vunbal Time On NDeviceNm_29736_Anlg Over KW Time Off NDeviceNm_29737_Anlg Over Ia Time Off NDeviceNm_29
284 PMCS Interface ToolkitI/O Real CommentDeviceNm_22559 PFLEAD_TOTAL NDeviceNm_22560 PFLAG_A YDeviceNm_22561 PFLAG_B YDeviceNm_22562 PFLAG_C YDeviceN
285I/O Real CommentDeviceNm_22739 KW_TD_MIN YDeviceNm_22740 FREQ_MIN YDeviceNm_22741 PF_LEAD_MIN YDeviceNm_22742 PFLAG_TOTAL_MIN YDeviceNm_22743 V1_TH
286 PMCS Interface ToolkitI/O Real CommentDeviceNm_22779 IB_THD_MAX YDeviceNm_22780 IC_THD_MAX YDeviceNm_22781 KVAR_TD_MAX YDeviceNm_22782 KVA_TD_MAX
287I/O Real CommentDeviceNm_23285 VNEG_SEQ_MAG YDeviceNm_23286 VNEG_SEQ_PHS YDeviceNm_23287 IZERO_SEQ_MAG YDeviceNm_23288 IZERO_SEQ_PHS YDeviceNm_2328
288 PMCS Interface ToolkitI/O Real CommentDeviceNm_28869 KVAR SWD #SUB INTERVALS YDeviceNm_28869_GWY KVAR SWD #SUB INTERVALS NDeviceNm_28870 KVA SWD #
289I/O Real CommentDeviceNm_29699 OVER_IC_DOOVER YDeviceNm_29699_GWY Over Ic Over Dropout NDeviceNm_29700 OVER_VUN_DOOVER YDeviceNm_29700_GWY Over Vun
290 PMCS Interface ToolkitI/O Real CommentDeviceNm_29739 OVER_IC_OFF YDeviceNm_29739_GWY Over Ic Time Off NDeviceNm_29740 OVER_VUN_OFF YDeviceNm_29740
291I/O Message CommentDeviceNm_4937 Ethernet_Subnet YDeviceNm_4938 Ethernet_DGateway YDeviceNm_22608 Analog1 Value YDeviceNm_22609 Analog2_Value YDevi
PMCS Interface Toolkit Back to Main Menu •••• iiiBack to Main MenuContentsINTRODUCTION...
22 PMCS Interface ToolkitElevation WizardsUsageElevation wizards are graphical elements that represent switchgear componentsuseful for creating 3-D el
292 PMCS Interface ToolkitI/O Message CommentDeviceNm_31309 Comm2_Baud YDeviceNm_31310 Comm3_Baud YDeviceNm_31311 Comm1_Protocol YDeviceNm_31312 Comm2
293Index2239 Motor Protection Relay, 171269 Plus Motor Management Relay, 87, 88, 1753369 Motor Management Relay, 1765565 Feeder Management Relay, 92,
294 •••• Index PMCS Interface ToolkitTTabular Data Screen Wizards, 11, 99Toolbar wizard, 24UUniversal Relay, 150Universal Relay Devices, 150UR, 150W
295(This page left blank intentionally.)
GE Industrial Systems General Elect
23Floor Plan WizardsUsageFloor Plan wizards are graphical elements that are useful for creating accuraterepresentations of a facility layout. You can
24 PMCS Interface ToolkitToolbar WizardUsageThe Toolbar wizard is a navigational tool which allows the user to move betweenrecently-used or frequently
25Annunciator Panel WizardUsageThe Annunciator Panel wizard provides an industrial-style annunciator display panel,consisting of a bank of 48 indicato
26 PMCS Interface ToolkitFrom the Event Logger’s perspective, there are two parts to configuring theAnnunciator Panel. First, each DDE Item that will
27Annunciator Panel WizardRelay 1(green)Relay 2(green)Relay 3(green)PMCSDDE ServerAnnunciator Panel Wizard monitors DDE Items at Event LoggerEvent Log
28 PMCS Interface ToolkitEach "Alarm indicator" as defined by the Event Logger will appear to InTouch as aDDE Integer item which can have th
29ConfigurationNote: Prior to configuring an Annunciator Panel Wizard, you should have completedconfiguration of the Annunciator Panel Items at the PM
30 PMCS Interface ToolkitDouble-click on the wizard to display the Annunciator PanelDialog:Complete the Annunciator Panel Name field (up to 8 characte
31Enter the text to display on any of the three lines available for the selected button. Itis not necessary to enter text on all three lines. Click OK
iv •••• Contents PMCS Interface ToolkitTroubleshooting Tips for the Annunciator Panel Wizard ...
32 PMCS Interface ToolkitTwo steps remain after the wizard has been configured.First, InTouch DDE Integer tags must be created for the DDE items confi
33An example of a simple script is shown below:Panel1_R1C1.Name = ANN_P_1A.Name;Panel1_R1C2.Name = ANN_P_1B.Name;Panel1_R1C3.Name = ANN_P_2A.Name;At r
34 PMCS Interface ToolkitTroubleshooting Tips for the Annunciator PanelWizard• Make sure that all DDE Items associated with the annunciator panelhave
35Custom Table WizardUsageThe Tabular Data Screen wizards provide the ability to view extensive device data intabular form. However, they do not allow
36 PMCS Interface ToolkitBegin configuring the Custom Table by completing the following fields:Field DescriptionDevice Name Enter the name of the devi
37EPM 7700 Users Only: When the EPM 7700 device type is selected, an additionalfield appears in the Custom Table Dialog box, adjacent to the Device Na
38 PMCS Interface ToolkitWhen these fields are completed, click the Select Multiple Tags button to selectseveral tags at once, or click the Select Tag
39 You may select OK to select this table configuration, or you may edit the tags one ata time using the Select Tag X buttons (for instance, if you wi
40 PMCS Interface ToolkitSystem Statistics WizardUsageThe System Statistics wizard is an informational tool which allows the user to viewdetailed stat
41The System Statistics wizard requires a name itself, and also the name of a DDEServer to access.By default, the System Statistics wizard assumes tha
PMCS Interface Toolkit Contents •••• vP Range Tab...
42 PMCS Interface ToolkitLockout/Tagout WizardUsageThe Lockout/Tagout provides a method for assigning danger or ground tag graphicsto various one-line
43Several PMCS breaker management devices support the Lockout/Tagout Wizard intheir Large Faceplate and Tabular Data Screen wizards. These devices are
44 PMCS Interface ToolkitComplete the following fields:• Enter the name of the Status Group associated with this Lockout/Tagoutsymbol. The Status Gro
45Breaker_Group_1 is the name of the Status Group we’ll assign to all wizardsassociated with this breaker; Tag Window is the name of the window we wan
46 PMCS Interface ToolkitWe name the Lockout/Tagout panel Panel_1. We associate the Panel with the sameStatus Group as our other wizards, Breaker_Grou
47The Installed By field on the tag shows the name of the current operator whoinstalled the tag; the Installed At field shows the time and date stamp
48 PMCS Interface ToolkitSpecial Scripting Considerations for the EPM 7700This section describes the special InTouch scripting which is required for t
49Installing the Application Script1. After configuring the EPM 7700 Large Faceplate wizard or Tabular Data Screenwizard, select “Special \ Scripts \
50 PMCS Interface Toolkit 1. Click the OK button to close the Application Script Dialog.NOTE: The application script text is only needed once for eac
vi •••• Contents PMCS Interface ToolkitSetpoints Tab...
52 PMCS Interface ToolkitEPM 7700 Large Faceplate or Custom Table Wizard ScriptingConfiguring the Large Faceplate/Custom Table Script1. After configu
54 PMCS Interface ToolkitEPM 7700 Tabular Data Screen ScriptingAll EPM7700 Tabular wizards require the creation of a Window Script in InTouch.The Wind
55Creating Floor Plans, ElevationViews, and One-Line DiagramsIntroductionThis chapter illustrates how to use the GE wizards described in Chapter 2 to
56 PMCS Interface Toolkit6. You can add additional navigation buttons (using standard InTouchcontrols) to open windows containing one-line views or o
57Floor PlansA floor plan should be a recognizable overhead representation of a facility. Thesewindows are built using the GE Floor Plan wizards, desc
58 PMCS Interface ToolkitElectrical One-Line DiagramsOne-line diagrams are built by placing and linking circuit elements using the One-Line wizards, t
59{ Set values of local discrete variables basedon state of integer status of breaker. Thissection sets the breaker status memorydiscretes to true if
60 PMCS Interface Toolkit{ set the bus status for the incoming feeds tothe dependent bus below in thedistribution hierarchy. The IF_THENstatements in
61Sample ApplicationCreating a basic interfaceWe’ve learned about the various parts and pieces of the Interface Toolkit; now let’sput it to work.Suppo
PMCS Interface Toolkit Contents •••• viiSetup Tab ...
62 PMCS Interface ToolkitFirst, we’ll create all our new windows and name them, then we’ll go back and fleshthem out with their contents and add link
63We’ll include a note about the panelboard’s location, describing where to find thereal panel, and also a note of instruction: “Click a device to see
64 PMCS Interface ToolkitNow we’ll develop the PQM Tabular data screen. Select the PQM Tab window anduse the Wizards tool to place the PQM Tabular Dat
65Complete the application by developing the Faceplate and Tabular screens for eachof the four trip units and that’s it — we’ve just developed a PMCS
66 PMCS Interface Toolkit(This page left blank intentionally)
67Features of GE Large FaceplateWizardsAbout the Large Faceplate WizardsThis chapter contains descriptions of the functions available with each of the
68 PMCS Interface ToolkitPOWER LEADER EPMThe large faceplate representation of the POWER LEADER EPM provides thefollowing animated functions:Click on.
69differ depending on whether the EPM is configured as Wye or Delta. Please note thatthe Normal Scroll Delta and Alternate Scroll Delta lists contain
70 PMCS Interface ToolkitAlternate Scroll, Wye Alternate Scroll, DeltaCurrent, Phase A Demand Current, Phase A DemandCurrent, Phase A Peak Demand Curr
71Spectra MicroVersaTrip Trip UnitThe large faceplate representation of the Spectra MicroVersaTrip trip unit providesthe following animated functions:
72 PMCS Interface ToolkitEnhanced MicroVersaTrip-C Trip UnitThe large faceplate representation of the Enhanced MicroVersaTrip-C trip unitprovides the
73The EMVT-C’s metering modes available with the SELECT button are as follows:Mode DescriptionAMPS Current, with no label in the units area of the dis
74 PMCS Interface ToolkitEnhanced MicroVersaTrip-D Trip UnitThe large faceplate representation of the Enhanced MicroVersaTrip-D trip unitprovides the
75The metering modes available with the SELECT button are as follows:Mode DescriptionAMPS Current, with no label in the units area of the display. Pha
76 PMCS Interface ToolkitPOWER LEADER MeterThe large faceplate representation of the POWER LEADER Meter provides thefollowing animated functions:Featu
77The parameters available with the SCROLL buttons are listed below:Mode DescriptionRMS Current Units in Amps; phase shifting among A, B, and C.RMS Vo
78 PMCS Interface ToolkitSpectra ECMThe large faceplate representation of the Spectra ECM provides the followinganimated functions:Feature FunctionDis
79Mode Parameters and UnitsSTATUS Motor StatusECM StatusTrip StatusSETPOINTS FLA Setting, ampsRating Plug, ampsPhase Unbalance, disabled/enabledGround
80 PMCS Interface Toolkit EPM 3710 MeterThe large faceplate representation of the EPM 3710 provides the following animatedfunctions:Feature FunctionDi
81Display Indication ParameterkW Total real powerkVA Total apparent powerkQ Total reactive powerPFLG or PFLD Power factor; lagging or leadingHz Freque
1IntroductionWelcomeThe PMCS Interface Toolkit is a POWER LEADER Power Management ControlSystem (PMCS) version 6.11a tool that provides a custom toolk
82 PMCS Interface ToolkitEPM 3720 MeterThe large faceplate representation of the EPM 3720 meter provides the followinganimated functions:Feature Funct
83Display Indication ParametersB, Phase B current and B-C line-to-line voltageC, Phase C current and C-A line-to-line voltage*, Average current line-t
84 PMCS Interface ToolkitEPM 7700 MeterThe large faceplate representation of the EPM 7700 meter provides the followinganimated functions:Feature Funct
85Screen Selected Description1 - Total Power• KW Total• KVAR Total• KVA Total• PF Signed Total2 - Three-Phase Measurements• Vln a; Vln b: n/a whe
86 PMCS Interface ToolkitScreen Selected Description7 - Per-Phase Minimums• Vln a Min; Vln b Min: n/a when Voltage Mode is DELTA• Vln c Min: n/a whe
87269 Plus Motor Management RelayThe large faceplate representation of the 269 Plus provides the following animatedfunctions:Feature FunctionDisplay W
88 PMCS Interface ToolkitFeature FunctionLINE Buttons Rotate among parameters within a page. Certain configurationsor meter values may prevent display
89Page Value Text Displayed Description1 PAGE 3: ACTUAL VALUESMOTOR CAPACITY DATAPage header2 ESTIMATED TIME TOTRIP = xxx SECONDS3 3 MOTOR LOAD AS
90 PMCS Interface ToolkitPage Value Text Displayed Description2 CAUSE OF LAST TRIPmessageMessage is a brief explanation of trip cause3 PRE-TRIP AVERAG
91Page Value Text Displayed Description7 4 3 PHASE KVARSKVAR = xxxDisplayed only if MTM unit is on line5 POWER FACTORPF = xxxDisplayed only if MTM uni