Connect the accessory kit to the through wiring.
Push wires into xture.
4
Snap in the terminal block to the factory mounted
holder. Be careful not to break the wires at a high
angle when pushing them inside the housing.
Through wiring
Luminaire Installation
With the supplied universal bracket the product
is compatible with the following USG type grids:
DX, DXI, DXT, DXF, DXM.
Reference diagram (right) to determine which
hole to use for a given grid.
Safety screw holes.
One is needed,
more are optional.
DX
DXT(F)
DXI
DXI
DXF
DXF
DXT(F)
DX
DXM/
DXT(G)
DXM/
DXT(G)
Preliminary Electrical Connections
1
Loosen cable gland nuts to insert AC line. Optionally,
insert dimming line into smaller cable gland.
2
Connect the AC line and dimming wires to the
terminal block of the line-in connector accessory:
Black to L1, White to N, Green/yellow to ground,
Grey to D1 and Violet to D2 for 1-10V or Orange to
D1 and Violet to D2 for DALI.
Note: Use BL Series CE Continuous Leader Cable (1-
10V) SKU 85601 or BL Series CE Continuous Leader
Cable (DALI) SKU 85675.
First unit only
AC line
Dimming line
(optional)
Line-in connector
accessory
Black
White
Green/yellow
Grey or Orange
Violet
Terminal block