10 | GE Oil & Gas
General Data
User Interface:
• HandheldCommunicator
• Pushbuttonsoperationwithdigitaldisplay
• ValVuesoftware
• ValVueAMS*snap-on
• ValVuePRM*plug-in
• DTMthoughanyFDT/DTMcompatiblehost
Level Transmitter/Controller:
• Levelorinterfacelevelmeasurement
• Specificgravitymeasurementanddisplay(onlywiththe
displacer fully immersed)
• Zeroandspandigitalcalibration:
- independent zero and span adjustment
- current loop range independent from zero/span calibration
(can be changed at any time without zero/span re-calibration)
- manual or automatic calculation for reduced span and zero
shift for interface service
• Self-tuningforsmartfiltering
• Selectablelowandhighlevelalarms
• Loworhighfailsafeoutputsignalimmediatelyactivatedin
case of a failure detection
• Continuousself-diagnosticwithbargraph
• Continuousdatarecord:numberoffillings,lowleveltime,
high level time, working time
• Configurationcheck:analysisof12400databasetoavoid
bad mounting, out of range use
• Storageanddisplayofalarmsthathaveappeared
• Outputcurrentgeneratorforloopcheck
Level Controller:
• P,I,D...advancedcontrol
• Remotesetpointandcontrolleroutput
• Lowandhighcontrolleralarms(absoluteanddeviations)
• ProcesstrendthroughValVuesoftwaresuite
Level Switches:
• Twobuilt-insolidstateswitches:1A-30VDCmax
• Configurable:lowandhighlevelalarms,faultorreset
occurred, instrument in failsafe…
Second 4-20 mA Analog Ouput:
• Secondlevelvariablemeasurement,usefultoconnectalocal
level indicator
Action:
• Directorreverseviasoftware
Output Signal Filtering:
• Firstorderfilteringofoutputsignalwithadjustabletime
constant
• Smartfilteringofcontactlesssensoroutputsignal,to
eliminate noise before digital signal processing
Software and Hardware Locks:
• Softwarelockforpushbuttons
• Hardwarejumperlockforfullprotectionagainstparameter
change
Instrument
Commentaires sur ces manuels