DEH40206 Installation Instructions
DESCRIPTION
The ProSys Lighting Control System is a small network of
relay panels and occupant control switches linked by a 4-wire
dataline. Together, these devices form a reconfigurable
switching platform — one that uses “softwiring” instead of
hardwiring to link occupant switches to relays.
There are four basic configurations of SWS (or dataline
switches): the single-gang, 1-, 2- and 4-button RS1PS-x,
RS2PS-x and RS4PS-x, respectively, and the two-gang,
8-button RS8PS-x.
Each switch includes a bi-color LED status light for each control
button and a locator light. In addition, the 2-, 4- and 8-button
units have directories which accept standard
3
8" wide (9mm)
labels. The x suffix in the catalog number refers to button and
switchplate color: 2 = ivory, 4 = almond, 7 = white and 9 = grey.
ProSys softwired switches are available with a key-
enabled override function. The switch will be disabled
except when a key is used to activate a 5 minute
override period. Dip switch 4 must be in the off position
to enable this feature as shown on page 8. Order this
feature by adding a -K to the part number for the 1- 2-,
4-, and 8-button switch. For example: RS2PSxK.
Any button on a Softwire Switch may be softwired to:
Any relay or group of relays within a single relay panel
A channel within a single relay panel
The same channel among multiple panels (requires an
RCLK8PS Softwired Clock, which also operates as a
handheld programmer)
Before starting, read the following installation
instructions. If you have questions, call GE Total
Lighting Control Service at:
1-877-584-2685 (LTG-CNTL) in the USA and Canada.
RS1SWS-x RS2SWS-x
RS8PS-xRS4PS-x
ProSys Lighting Control System
Catalog Number RSxPS-x
GE Total Lighting Control
ProSys Softwired Switches, 1-, 2-, 4- and 8-button
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with
installation, operation or maintenance. Should further information be desired or should particular problems arise that are not covered for the purchaser's purposes,
the matter should be referred to the GE Company.
Vue de la page 0
1 2 3 4 5 6 7 8 9 10

Résumé du contenu

Page 1 - GE Total Lighting Control

1DEH40206 Installation InstructionsDESCRIPTIONThe ProSys Lighting Control System is a small network ofrelay panels and occupant control switches linke

Page 3

2DEH40206 Installation InstructionsThe dataline connects relay panels, softwired switches andoptional control modules. Within the 4-wire dataline are

Page 4

3DEH40206 Installation InstructionsThe 1-, 2- and 4-button dataline switches mount in standardsingle-gang switch boxes. The 8-button unit mounts in as

Page 5 - Patterns or Scenes

As shown in Figure 1 below, dataline switches are numberedsequentially beginning with 01-01 (Panel 01-Switch 01). Asingle switch unit may have 1, 2, 4

Page 6 - SWITCH BUTTON LABELING

SOFTWIRING A DATALINE SWITCH TO A GROUP OF RELAYSPatterns or ScenesAny dataline switch may be configured as either anON/OFF Group Switch or a Pattern

Page 7 - " 4 -03 WALL WASH

6DEH40206 Installation InstructionsSWITCH BUTTON LABELINGThe individual switch buttons provide space for 3⁄8" wide x 11⁄16"long (9mm x 30mm)

Page 8 - SPECIAL FUNCTIONS (CONTINUED)

7DEH40206 Installation Instructions01-0101-0201-03SPECIAL FUNCTIONSProSys is designed to provide flexibility without compromisingsimplicity in install

Page 9 - 2 on Cleaning Switch to turn

8DEH40206 Installation InstructionsALL ON/ALL OFFTo convert to All ON/All OFFoperation, DIP switch 1 is moved tothe OFF position (1 OFF, 2 ON). Thisop

Page 10

9DEH40206 Installation InstructionsCleaning SwitchThe third DIP switch, when set inthe OFF position as shown, changesthe operation of the entire switc