SOFTWARE OVERVIEW
P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE 4–5
Parity: The parity can be selected as "Odd", "Even", or "None". This is a simple error
check method capable of detecting single bit communication errors on a serial
network (i.e. the sub-network).
Data bits: There can be "7" or "8" data bits. Generally, 8 data bits are used. This
parameter determines how many bits per byte of user data that is transmitted on the
sub-network, excluding start, stop and parity bits.
Stop bits: There can be "1" or "2" stop bits. Determines the number of stop bits at the
end of each byte sent on the sub-network.
DEVICE TYPES The third step in the configuration wizard introduces device types into the project and
configures their parameters. Every device must be unique. Predefined devices can be
loaded from a file, and it is possible to connect devices to the sub-network at a later step in
the wizard. Additional devices can be created by editing previously saved devices.
The device types window is shown below.
The Modbus address range, including bit areas and register areas (words), is shown below.
The Modbus commands are also shown for the corresponding memory areas. Note that
many device manuals ignore the leading digit of the address (i.e. 0, 1, 3 or 4); as such, the
address 40001 is often referred to as 0001. The leading digit can be determined from the
Modbus command specified.
Users should consult the instruction manuals of the various network devices to determine
the actual Modbus command code(s) implemented or required. This will determine the
implied leading digit of the data address (i.e. 0, 1, 3 or 4).
In most GE Multilin relay and meter documentation, Modbus addresses are indicated in
hexadecimal form. For the Modicon format used for the P485, convert the hex address to
decimal, add 1, then append a prefix of 1, 2, 3, or 4, depending on the type of register. For
example, to convert the input register hexadecimal address 0x0300, we have:
1. 0300h = 0768 decimal
2. 0768 decimal + 1 = 0769 decimal
3. change 0769 30769 (prefix “3” for input registers)
Therefore, a Modbus hex address of 0x0300 is 30769 in Modicon format.
Address Command
0x Output coil (bits) 00001 to 09999 #1 (decimal): Read coil status
#15 (decimal): Force multiple cells
1x Inputs status (bits) 10001 to 19999 #2 (decimal): Read input status
3x Input status (word) 30001 to 39999 #4 (decimal): Read input registers
4x Output (word) 40001 to 49999 #3 (decimal): Read holding registers
#16 (decimal) Preset multiple registers