CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP
50
EPM 5000 series Advanced Power Meters GE Multilin
9.7: Relay Mode
NOTE: Relays are not available for the EPM 5200P.
SWITCH DESCRIPTION Segment Position
A Reversal Imbalance Control UP!Enable
DOWN!Disable
B AND/OR Logic UP!AND
DOWN!OR
C & D Relay Control see Table 8-4
Table 9-3: SWITCH PACKS for 04P & 05P
The Switch PACKS in FUNCTIONS 4 and 5 of programming GROUP 0 control the relay position. Setting
the switches in different combinations allows the user to specify the conditions in which the relay will be
“SET” or “RESET.” The following table indicates possible configurations.
SWITCH C SWITCH
D
DESCRIPTION
UP UP FAIL-SAFE MODE—The normal or non-event condition is set. RESET relay
on either out of limit condition. Relay acts as a protective switch if power is
interrupted. This alerts the user if the meter or the meter power is out.
UP DOWN N/A (Reserved for future features).
DOWN UP N/A (Reserved for future features).
DOWN DOWN RESET MODE—The normal or non-event condition is reset. SET relay on
either out of limit condition.
Table 9-4
DEFINITIONS:
RESET: There is a short between “COM” and “N.C.” (Normally closed)
SET: There is a short between “COM” and “N.O.” (Normally open)
(See Part I: Installation and Operation.)
Example 1: Fail-safe mode normally set—non-event condition is set relay
Relay 1 will be “SET” if the instantaneous reading for frequency is between 58 Hz and 62 Hz. When all
other conditions exist, the relay will “RESET.”
NOTE: Under this setup the relay acts as a protective switch.
58 Hz
62 Hz
0 Hz
RESET
RESET
L 1
L 2
SET
NO POW ER TO THE UNIT
RESET