Through-the-wall installation.
Read these instructions completely and carefully.
Preparation of the Opening in the Wall
Make certain a wall receptacle is available close to
the hole location or make arrangements to install
a receptacle.
The cord length for the 115-volt models is 72 to
the right and 47 to the left.
For the 230/208-volt models the cord length is
65 to the right and 39 to the left.
1
Support Requirements for the Air Conditioner
The air conditioner wall case may be installed
flush with the inside wall or flush with the
outside wall.
The finished sides of the opening should be
structural wall members.
Lintel—
Use a lintel in brick veneer and brick and
block types of wall to support the bricks or blocks
above the opening. Do not allow the wall case to
be used in lieu of a lintel.
Flashing—
Install flashing (drip rail) as shown to
prevent water from dripping inside the wall and
down the outside of the building.
2
Support Requirements for the Air Conditioner
Mortar between the case and the brick all around
the case may be undercut at about 45° for
improved caulking.
3
Caulking
Top of case
Inside
Outside
Undercut
mortar
Trim
molding
(if desired)
Plaster
line
Caulking
(above &
below the
flashing)
Flashing
(drip rail)
1/4 min. extension
inside the wall from
the trim molding
Room side
Brick veneer
Lintel angle
(if required)
Caulking
(on all 4 sides
on the outside
of the case)