Status Code List
Status Screen
RTOS_
SCHEDULING
Operating Sys-
tem Fault.
An internal
error from
which the
device recov-
ered automati-
cally
2
SUPPLY_
HIGH
High Air
Supply
Warning
Supply Pres-
sure above
upper limit.
1 1:A failure in the air filter
regulator occurred.
2: A nearby equipment
drawing a high volume,
suddenly quit using air and
created a spike in air supply.
3: The air set is adjusted
greater than configured
threshold.
1: Replace air filter regula-
tor.
2: Resize air manifold.
3:Adjust threshold to be 3
to 5 psig greater than set
air supply.
BIAS_OUT_
OF_RANGE
Bias Out Of
Range
An important
internal
parameter is
out of range.
1 The servo signal to the cur-
rent to pressure converter is
outside of normal throttling
range.
IP_OUT_OF_RA
NGE
I/P Out Of
Range
I/P current
feedback is out
of range.
1 The loop current to the
internal current to pressure
converter is outside of nor-
mal range.
TEMPR_OUT_O
F_RANGE
Temp. Out Of
Range
Temperature
outside oper-
ating range.
2 The board temperature is
below –40 °C or above
85 °C.
NOT IMPLEMENTED
DI_
ABNORMAL
3
LATCH_
FSAFE
TIGHT_SHUTO
FF
NVM_CHECKS
UM0
NVM Check-
sum Error
The device
failed to read
critical data
from non vola-
tile memory.
1 A permanent corruption of
the content in non volatile
memory occurred.
1: Remove power to the
device for 2 minutes and
restart the device.
2: If the failure persist,
replace the device.
Table 8 Fault Matrix (Continued)
FAULT Name TEXT For DD &
ValVue
HELP For DD &
ValVue
Critic
ality
Probable Cause Recommended Action