ValVue Digital Communications Software Ver. 2.80
480
GE Oil & Gas
Buttons and Fields
Hart Master
Master Mode Use the pulldown list to select the HART mode as either:
Primary: This the default
Secondary
This is the HART Master mode used by the VECTOR when communicating as a HART
master with wired-HART devices.
Retry Count Enter the number of retries to establish communication before failure.
Device Scan Mode
Sub-Device Scan On
Power-up
Use the pulldown list to enable or disable scans automatically on powerup.
When enabled, the VECTOR scans the 4-20 mA loop for attached HART devices on
power-up or when the VECTOR is reset. These devices are added to the list of sup-
ported sub-devices for the VECTOR and are communicated to the WirelessHART
gateway.
The VECTOR can support a maximum of eight sub-devices. If more than eight
wired-HART devices are detected, only the first eight devices are used.
Scan Start Address Enter the start address for the scan.
Scan Start Address Enter the stop address for the scan.
Sub-Device Time
Sync
Use the pulldown list to set so that when you scan you synchronize the subdevice
times with the scanning device.
Polling Address Enter the address. This is the HART polling address used to communicate to the VEC-
TOR on the wired-HART interface using a HART capable host (such as a HART com-
municator or PC with HART modem).
By default, the VECTOR is at HART polling address 15. Range: 0 and 63.