Configure Tab
Configure Tab
From the Configure tab you can set the information that tells the SVI how the valve/actuator
is configured.
Figure 6 Configure Tab
Fields
Polling Address HART can communicate with up to 15 devices on a single pair of
wires. These devices are distinguished by their polling address
which is a number from 0 to 15. If there is a device at polling
address 0, it must be the only device on the loop. There may be up
to 15 devices with non-zero polling addresses on the loop (subject
to power and intrinsic safety constraints). Devices which operate
4-20 mA are generally required to have polling address 0, however
with split range valve positioners, several4-20 mA devices may be
wired in series. These devices should be set up with non-zero poll-
ing addresses.
Switches The SVI can measure the status of too contact switches (open or
closed). See the operating manual for connection information.