Menu - Diagnostics
$$Friction - The friction measured from a standard actuator signature
$$FLowerSpringRange - The lower spring range measured from a standard actuator
signature
$$FupperSpringRange - The upper spring range measured from a standard actuator
signature
$$LowPressureActual - The pressure when the actuator is exhausted
$$HighPressureActual - The supply pressure
$$Speed - The speed at which the last diagnostic test was run
$$SpeedSaved - The speed at which the saved standard signature was run
$$SpeedBaseline - The speed at which the baseline standard signature was run
$$LowerSpringRange, $$LowerSpringRangeSaved, $$LowerSpringRangeBaseline - The
lower spring range calculated from the current, saved, or baseline standard signature
$$UpperSpringRange, $$UpperSpringRangeSaved, $$UpperSpringRangeBaseline - The
upper spring range calculated from the current, saved, or baseline standard signature
$$Signature - The position/pressure pairs gathered during the standard signature test
$$SignatureSaved - The position/pressure pairs saved in the saved standard signature
$$SignatureBaseline - The position/pressure pairs saved in the baseline standard signature
Menu - Diagnostics
When you right-click on the Diagnostics tab, a context menu appears. The items depend
upon what diagnostics have been run:
View Diagnostic Graph - Views the data from the last run diagnostic procedure.
Save Diagnostic Data - Saves the data from the last run diagnostic into a disk file. The
disk file can be imported into spreadsheets or read with ValVue.
Diagnostic Report - Opens a dialog to select a .dgn file and specify specific group
data (up to three of the same type) for presentation on a diagnostic report.
Save Signature in SVI2 - Saves the current signature in the SVI2.
Save Signature as Baseline in SVI2 - Saves the current signature as the baseline
signature in the SVI.
Reset Continuous Diagnostics - Resets the continuous diagnostic data (stroke count,
cycle count, time open, time closed, and time near closed) to 0. When reset, the
previous values are lost, thus the data should be recorded somewhere before being
reset if it is to be used.
Detach Trend - Removes the trend display from the tabbed dialog and creates a
separate trend display.
Help - Displays the help file at the Diagnostics tab instructions.