ValVue Digital Communications Software Ver. 2.80
452
GE Oil & Gas
2. Click and a second dialog appears.
3. Click again and a dialog that says Device reset OK appears.
4. Click again and a dialog that says NOTE Loop may be returned to
automatic control appears.
5. Click .
Report Setup
One of the functions available on the Overview tab is the ability to generate reports. ValVue
VECTOR provides the ability to extract information about the VECTOR operation and dump the
information into a report format. When extracted the information from a device requires a
template file into which to dump the data. To generate a report with ValVue VECTOR you must
first create a report template file that includes the parameters you would like to include in the
report as well as personalization.
How to Create Reports
There are three basic steps to create reports:
1. Set up the report: Create a report template file.
2. Select the report setup (report template file): Using the Report Setup command from the
Monitor context menu.
3. Generate the report: Using the Report command from the Tools or context menu.
Creating Report Template Files
You can create a custom report by creating a rich text format (RTF) file which is laid out in the
format of the desired report. The default template is located in:
Win7 and 2008 Server: C:\Program Data\Dresser\ValVue\VECTOR\Report.
WinXP and 2003 Server: C:\Documents and Settings\All Users\Application
Data\Dresser\ValVue\VECTOR\Report.
Prior to selecting the set up of the report you must create the report template file in an rtf
format. The report template includes the operation parameters that you would like populated
in the report.
ValVue VECTOR substitutes the values of parameters into the text file where ever it finds a
parameter name that matches a VECTOR parameter. For each parameter you would like
included in the report place $$ in front of the parameter name.
For example:
Tag = $$Tag