Calibrate Context Menu
Calibrate
Calibrate Context Menu
When you right click on the Calibrate tab the Calibrate Tab Context Menu appears.
Figure 48 Calibrate Tab Context Menu
The following items are on the Calibrate context menu.
Run Find Stops: Runs the automatic position calibration process ( “Run Find Stops” on
page 248).
Manual Find Stops: Set the position calibration by moving the valve full closed and full
open. On very large valves, the automatic find stops routine may timeout before the
valve has reached the end of travel. Manual find stops allows calibration of these
valves ( “Manual Find Stops” on page 250).
Open Stop Adjustment: See “Open Stop Adjustment” on page 246.
Only Detach Trend and Help are available in the Calibrate context menu
for Normal and Manual modes.