Diagnostics Tab
Figure 11 Positioner Signature
A Positioner Signature produces an input signal vs. position graph
for both increasing and decreasing signal. The signal is a simulated
signal so linearity cannot be checked.
To run a Positioner Signature: Enter a starting current, an ending
current, and the number of samples that should be taken across
the interval specified by the starting and ending current.
The positioner is slowly moved from the starting position to the
ending position and back and the two curves (up and down) are
measured and displayed.
Step Profile: A series of step tests are performed starting
from the start position and moving toward the end position.
Each step test is a step whose length is specified in the step
parameter. Step tests are performed one after another until
the end position is reached. If two way is selected, step tests
are performed in the reverse direction as well. The time
parameter determines how long the valve position is
sampled at each step test.)
Starting position
Ending position
Sample time - Number of seconds to sample at each
step
Step length - The % position change at each step - 0
means to step the full distance from starting position to
ending position