ValVue Digital Communications Software Ver. 2.80
154
GE Oil & Gas
RAM_CHECKS
UM
RAM Check-
sum Error
An internal
error from
which the
device recov-
ered automati-
cally.
2 A corruption of the content
in volatile memory
occurred.
Notify the factory at svi-
FW_
CHECKSUM
Flash Check-
sum Error
A critical inter-
nal fault.
1 Invalid firmware checksum
due to data corruption.
1: Remove power to the
device for 2 minutes and
restart it.
2: If the failure persists,
Replace device.
STACK Stack Error An internal
error from
which the
device recov-
ered automati-
cally.
2 A problem with the memory
stack occurred.
Clear the condition using
ValVue or HART Host.
FACTORY-
WRITE
Factory Write
Indicator
Indicator of
writes to non
volatile mem-
ory allowed
only for firm-
ware upgrade.
1
NVM_TEST NVM Test Error An error in non
volatile mem-
ory could not
be repaired.
2 A problem occurred when
testing non volatile mem-
ory.
Clear the condition using
ValVue or HART Host.
0ESD Trip
occurred and
requires user
intervention to
be released.
FACTORYMODE Factory Mode
Indicator
Device per-
forms factory
authorized
operations.
1 Device is in the factory
mode.
Replace device and report
the problem at svisup-
port@GE.com.
REF_
VOLTAGE
Ref Voltage
Fault
May indicate
faulty A/D sub-
system.
1 A component problem is
affecting the circuit board's
reference voltage.
Replace device and report
the problem at svisup-
port@GE.com.
Table 8 Fault Matrix (Continued)
FAULT Name TEXT For DD &
ValVue
HELP For DD &
ValVue
Critic
ality
Probable Cause Recommended Action