ValVue Digital Communications Software Ver. 2.80
158
GE Oil & Gas
LINKAGE_DRIF
T
Linkage Drift 2 1:In the fully open or fully
closed position a raw travel
sensor count deviation of
x% exists against the cali-
brated stop value.
1: Verify that linkage is well
fastened.
2: Re run the Find Stops
method. When device goes
in Failsafe when running
the Find Stop method,
clear alarm and rerun the
stops.
VALVE_
STUCK_
CLOSED
Valve Stuck
Closed
Measured fric-
tion is below
customer
specified
range.
2 1: A handwheel is left
engaged.
2: Valve is seized in place.
3: Insufficient actuator
thrust.
1: Verify presence of a
mechanical stops such as
a handwheel.
2: Repair valve.
3: Run a PST or Extended
signature. If friction is
abnormal then overhaul
valve.
VALVE_
STUCK_
OPENED
Valve Stuck
Opened
Measured fric-
tion is above
customer
specified
range.
2 1: A handwheel is left
engaged.
2: Valve is seized in place.
3: Exhaust port is clogged
up (no venting).
4: An accessory prevents
the air from the actuator to
be vented.
1: Verify presence of a
mechanical stops such as
a hand wheel.
2: Repair valve.
3: Verify that exhaust port
is not restricted.
4: Run a TBT test from Val-
Vue. A failure of the TBT
test would indicate a prob-
lem in venting.
UI_OFF UI_OFF Pressure to
move valve is
greater than
customer
specified
range.
2
RANGE3 Range 3 Supply pres-
sure drop
exceeds a cus-
tomer speci-
fied value.
2
RANGE4 Range 4 PST canceled
before com-
pletion.
2
Table 8 Fault Matrix (Continued)
FAULT Name TEXT For DD &
ValVue
HELP For DD &
ValVue
Critic
ality
Probable Cause Recommended Action