ValVue Digital Communications Software Ver. 2.80
122
GE Oil & Gas
Signal Calibration Procedure
Use the Calibrate screen to recalibrate the signal sensor in the SVI II AP. The sensor is
calibrated at the factory and does not usually require recalibration, but if needed, this dialog
provides a convenient method.
NOTE The Reset to Factory selection in the Calibrate right click menu
returns the calibrations to those that were set at the factory.
The currently measured value of the primary input is displayed and can be compared to
reference signals to see if recalibration is necessary. Calibrating the primary signal can be
done most easily with a variable current source.
ValVue allows you to perform a low signal and high signal calibration.
Low Signal Value Calibration
1. Click Calib. Signal (Figure 94).
Figure 94 Starting Signal Calibration
Figure 95 appears indicating that the calibration will be changed.