ValVue Digital Communications Software Ver. 2.80
144
GE Oil & Gas
Diagnostic Info for Step Test
Click Show Diagnostic Info displays the analysis for each step (Figure 123).
Figure 124 Step Test Diagnostic Information (Diag Info)
Ramp Test
The Ramp Test produces a position vs. input signal graph for both increasing and decreasing
signal. The signal is a simulated signal so linearity cannot be checked.
1. Select Ramp Test and Ramp Test parameters become active to the right of the Diagnostic
Tests.
2. If necessary, adjust the following parameters:
Start Signal (mA)
Stop Signal (mA)
Number of Samples
3. Click Perform Diag. Figure 125 appears.
Figure 125 Ramp Test Running