ValVue Digital Communications Software Ver. 2.80
628
GE Oil & Gas
Pressure
Units
You can select the units in
which
the actuator pressure is reported.
Selections are psi, bar, or kpa.
Position Fault
Limits
You can configure how position errors are handled. A position error
occurs when the valve position differs from the requested position
(from the input signal in normal operating mode or the manual set-
point in manual mode) by more than the Position Error Band for more
than the Position Error Time 1. When this occurs, a status flag is set
which is reported during the next HART message (only that a flag is
set is reported. You can send a Read Status message to find out the
cause of the status flag). If the error persists for Position Error Time 2,
the valve is put in failsafe position. This latter action may be disabled
by unchecking the Enable box next to the Time 2 entry.
For practical considerations, Time 2 (if enabled) must be larger than
Time 1 by at least 2 seconds. Time 1 should be at least as long as the
time required to open the valve fully or unnecessary position errors
are reported. The maximum time is 327 seconds.
Characterization
Control valves are often
characterized
to give a specific
relation-
ship
between
flow
capacity (Cv) and percent opening
of
the
valve.
The valve can
be
characterized
with special purpose trim or with
the SVI positioner. Several
characterizations
are
available:
Linear:
Causes the valve to open
proportionally
with the
input signal. This option should be selected if non-linear trim
is used in the valve.
Equal Percentage (50)
and
Equal Percentage (30):
Two
equal
percentage
characterizations
are available, one with R=50
and the other with
R=30.
Quick Opening: The quick opening
characterization
is the
inverse of the Equal Percentage (50)
characterization
curve
.
Custom Configuration:
Selecting
this option
displays
an
additional
dialog where
you can enter or draw a
custom
characterization
curve. The
curve
can have up to nine
points and points in between are linearly
interpolated.
Air Action: Air-to-Open
I
Air-to-Close
You must select whether the valve is an air to open valve or an air to
close valve. This selection determines whether an increasing signal
opens or closes the valve.
Actuator Type:
Single/
Double
Selects the actuator type
-
single acting or double acting. This is
available
only on SVI2
Version
1.2.2 and later.