GE MN-ValVue-v2-8-IOM Manuel de service Page 160

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 660
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 159
ValVue Digital Communications Software Ver. 2.80
160
GE Oil & Gas
I/P LIMIT I/P current too high or too low Warning Electronic hardware
TEMP ERR Internal circuit temperature high (>80 °C, 176
°F) or low (<-40 °C, -40 °F)
Warning Environment
NVM ERR_R An FRAM record and its copy both have CRC
errors
Failsafe
RAM ERR RAM data item had a bad checksum Warning
FLASH ERR Flash memory failed checksum test Failsafe Flash memory failed check-
sum test
STACK ERR A valid hidden record (in RAM) existing upon
reset indicating that a stack overflow had
occurred
Warning
FCTRYMODE Factory mode failure Failsafe
NVM ERR-T An FRAM record and its copy both have CRC
errors
Warning
REF VOLT Temperature compensated I/P current is out
of range
Failsafe
POS SENSR Internal error in Hall Effect sensor Warning Electronic hardware
SIG SENSR Internal error in sensing of 4 - 20 mA Warning Electronic hardware
PRES1 ER Temperature compensated pressure
sensor 1 reading is outside the range
Warning
PRES2 ER Temperature compensated pressure
sensor 2 reading is outside the range
Warning
PRES3 ER Temperature compensated pressure sensor 3
reading is outside the range or supply pres-
sure recorded is >120 psi (8.28 bar, 828 kPa)
Warning
PRES4 ER Temperature compensated pressure sensor 4
reading is outside the range or pilot pressure
recorded is >120 psi (8.28 bar, 828 kPa)
Warning
PRES5 ER Temperature compensated pressure sensor 5
reading is outside the range
Warning
NVM ERR-W Writer to FRAM fails or data repairing in FRAM
fails
Warning
Table 9 LCD Error Messages (Continued)
LCD Description Action Cause
Vue de la page 159
1 2 ... 155 156 157 158 159 160 161 162 163 164 165 ... 659 660

Commentaires sur ces manuels