GE MN-ValVue-v2-8-IOM Manuel de service Page 128

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 660
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 127
ValVue Digital Communications Software Ver. 2.80
128
GE Oil & Gas
The Advanced Tuning Parameters dialog appears (Figure 106). Refer to Table 7 for
parameter descriptions.
Figure 106 Advanced Parameters Dialog
Table 7 Advanced Tuning Parameters
Tuning Parameter Description
Dead Zone When the valve position is within the setpoint +/- the dead zone, no additional posi-
tion control is performed. This value is normally 0%, however for high friction valves
(e.g. valves with graphite packing) a higher dead zone (%) helps avoid limit cycling
due to the stick/slip action of the valve. In these cases the dead zone chosen might
be 0.5% to 1%. Range: 0 and 5%.
Beta Beta is nonlinear gain factor, ranging from -9 to 9. When beta is 0, the position con-
troller gain is linear. Otherwise the gain is function of error. The larger the Beta, the
smaller the gain for small error. Typical values for a valve position controller is 7 or 8.
Position Compensation
Coefficient
The response of a valve is different when it is nearly closed than when it is nearly
open. The position compensation coefficient, a number between 2 and 20, allows
you to make adjustments to try to equalize the valve response. The normal value is 6.
Boost The boost field in the PID adjustments controls a supplemental pressure or boost to
speed up initial valve response. Valve response is the amount of time it takes for the
valve to go from setpoint to 100%
Stroke Time Amount of time in seconds required for the valve to be completely stroked.
Vue de la page 127
1 2 ... 123 124 125 126 127 128 129 130 131 132 133 ... 659 660

Commentaires sur ces manuels

Pas de commentaire