Status
Read Controller PID Displays the process controller PID parameters: P, I, Kt , Kd, and
Beta. Available only in version 5.11 and higher.
Read Setpoint Scale Displays the controller setpoint scale. Available only in version 5.11
and higher.
Response
The HART command response from the HDLT is displayed in the response box.
Status Code List
The following status messages report events since the last time the status codes were
cleared.
Startup – The level was powered off and restarted or a reset occurred.
Sensor Disconnected – The sensor was disconnected.
Sensor Fault – An invalid sensor reading was detected.
Torque Sensor Error – An invalid sensor reading was detected.
TCIR Reference Error – An invalid internal reference voltage was detected.
Torque Sensor Range Error – The torque sensor measurement was out of range.
EEProm Write Error – An attempt to save data to the non-volatile memory failed.
Data Overrun Error – An internal software/hardware error occurred.
Timeout Error – An internal software/hardware error occurred.
Circuit Temperature Error – The circuit temperature was outside of the operating
range.
Circuit Temperature Sensor Error – An invalid temperature sensor measurement was
detected.
Software Error – An internal software/hardware error occurred.
No Refresh – An internal software/hardware error occurred.
LOW ALARM – The level is lower than the lower alarm setting.
HIGH ALARM – The level is higher than the upper alarm setting.
Displacer Height Error – The displacer position was out of range.
Mounting Error – The level head is mounted incorrectly (compared to calibration and
configuration settings).
Specific Gravity Out of Range – The measured specific gravity is out of range.
Displacer Error – An invalid displacer measurement was detected.
Calibrate Failed – Calibration failed, probably due to an invalid data entry.
Low Alarm Occurred – The level was lower than the lower alarm setting (but may be
above the limit currently).