Mux Setup
ValVue Setup
Figure 30 Device Address
3. Enter a number between 1 and 31 for the desired node and select OK and Figure 31. The
node address must match the DIP switch setting on the Mux hardware.
The Multiplexor Setup dialog appears (Figure 31).
Figure 31 Options and Mux Setup
Buttons and Fields
Tag Enter up to eight characters long and is used to identify the MTL
multiplexor node in the system. The tag is displayed in Device List
box on Connected Devices screen.
Descriptor Enter a description with up to 15 characters for the MTL multi-
plexor node.