ValVue Digital Communications Software Ver. 2.80
550
GE Oil & Gas
Controller Alarms This box displays the status of the process variable alarms. The
alarms may be absolute or deviation alarms:
Absolute alarms: If the process variable is below the lower
alarm limit or above the upper alarm limit, the alarm light
turns on.
Deviation alarms: If the difference between the setpoint and
the process variable is below the lower alarm limit or above
the upper alarm limit, the alarm light turns on.
Controller Level/Setpoint
Display
This graphical display shows the current value of the level or the
interface as a green bar and the setpoint as a triangle. From this dis-
play, you can drag the triangle to change the setpoint when the con-
troller is in normal operating mode (local mode).
Controller Local/Manual If the controller is in Normal operation mode (local mode), you can
change the setpoint from LevelVue by dragging the indicator on the
Level/Setpoint display or by entering a setpoint directly. The control-
ler adjusts the output signal to try to match the process variable with
the new setpoint.
In Manual mode, the controller output is locked to a constant value.
You can change that value by dragging the indicator on the output
display or by entering a value directly.
Controller On/Off Turns the process controller on or off:
If not enabled (off), the HDLT operates as a normal transmitter.
If enabled (on), the HDLT performs the function of a controller
and the 4-20 output is a control signal to control a valve.
Controller Output Displays the output of the controller in percent.
Menu - Controller
When you right-click on the Controller tab, a context menu appears. The items that appear
depend on the HDLT mode:
Local Setpoint – Puts the controller in local setpoint mode. You can adjust the setpoint
in this mode.
Set Manual Mode – Puts the controller in Manual mode.
Report Setup - Allows you to select a report file and a report printing program.
Report - Generates a report of the HDLT parameters.
Detach Trend - Removes the trend display from the tabbed dialog and creates a
separate Trend display.
Help - Displays the help file at the Monitor tab instructions.