GE MN-ValVue-v2-8-IOM Manuel de service Page 610

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 660
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 609
ValVue Digital Communications Software Ver. 2.80
610
GE Oil & Gas
Alarm Type
Determines whether the alarms will
be
absolute
or
deviation:
An absolute alarm appears when the process variable
is
not
between the low and high alarm
values.
A
deviation alarm appears when the process variable differs from
the setpoint by more than the low and high alarm
values.
Controller Parameter List
The following parameters for the process controller can be changed whenever the process
controller is operating:
Proportional Gain (%) P is the ratio of proportional action (part of controller output) to error.
Integral Time (sec) Integral time or reset time, is the time constant of integral control.
Derivative Time (msec) Derivative time or rate time is the time constant of derivative control.
Derivative Gain Derivative gain is a parameter for derivative control. Typical range is
8 to 16.
Beta This is nonlinear gain factor, ranging from -9 to 9. When beta is 0, the
controller gain is linear. Otherwise the gain is the function of error.
The larger the beta, the smaller the gain for small error.
Setpoint Low and High
Limits
The setpoint is constrained to be between the low and high limits.
Both local and remote setpoints are limited. The limits are entered in
the same engineering units as the process variable.
Ratio Gain and Bias In ratio control, the setpoint and process variable can be in different
engineering units or on different scales. The relationship between the
setpoint in process variable units and the raw setpoint is given by:
Setpoint (in process variable units)=Ratio Gain x Setpoint + Ratio Bias.
The setpoint in process variable units is used in the PID calculation to
compute error.
Low and High Alarm Limits Defines when the alarm lights on the controller view are lit. If abso-
lute alarms are selected and the process variable is not between the
low and high alarm limit, the alarm light is on. If deviation alarms are
set and the difference between the setpoint and the process variable
is not between the low and high alarm limit, the alarm light is on. The
alarm limits are entered in the same units as the process variable.
Manual Reset Bias Only applies to P or PD control. It is the process controller output at a
typical operating steady state. If the controller outputs range from
30 to 50% at normal operation, the Manual Reset Bias should be set
at 40% in order to minimize steady state error.
Output Rate Limit Limits how fast the output can change. It is expressed as the percent
of full output range per second and can be between 1 and 200 per-
cent.
Vue de la page 609
1 2 ... 605 606 607 608 609 610 611 612 613 614 615 ... 659 660

Commentaires sur ces manuels

Pas de commentaire