GE MN-ValVue-v2-8-IOM Manuel de service Page 649

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 660
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 648
649
Diagnostic Reports
$$Pressure - Actuator pressure
$$IPOutput - The signal to the I/P in counts (0 - 65000)
$$Temperature - Circuit board temperature
$$LowTemperature - The lowest operating temperature that the device has encountered
$$HighTemperature - The highest operating temperature that the device has encountered
$$Output – Output - From the process controller
$$Mode - SVI mode
$$SignalPercent - Input signal as percent
$$AirAction - Air-to-open/Air-to-close
$$ActuatorType - Single/double acting actuator
$$PosErrorBand - Position error band
$$PosErrorTime - Time until position error
$$ PosErrorFailTime - Time until position error produces failsafe action
$$Charact - Characterization (linear, equal percentage, etc.)
$$CustomCharact - Displays the custom characterization constants (individual items of the
characterization curve may be selected by entering
$$CustomCharact[n] where n is a number between 0 and 17
$$ButtonLock - Button lock level
$$Bumpless - Bumpless Transfer on/off
$$BumplessSpeed - The time to move from manual to operating mode
$$TightShutoff - Tight shutoff on/off
$$TSValue - Tight shutoff value
$$ULimitStop - Upper position limit on/off
$$ULSValue - Upper position limit
$$LLimitStop - Lower position limit on/off
$$LLSValue - Lower position limit
$$NearClosed -Value below which is considered near closed
$$PosUnits - Position units of measure (always %)
$$PresUnits - the pressure units (psi, bar, or kpa)
Vue de la page 648
1 2 ... 644 645 646 647 648 649 650 651 652 653 654 ... 659 660

Commentaires sur ces manuels

Pas de commentaire